Summary

Investigation of a pipeline rupture during preparations for hot work at WC-294. The report identifies an unverified well shut-in, overlooked SCADA warnings and a shared solenoid that defeated pressure shutdown functions. It discusses deficient shutdown procedures and testing, and recommends verifying satellite well closure before closing the host facility’s incoming valve.

Topics

About This Record
Original title
11-12-2006 07:00 G04090 WC/294 Explosion - Incident >$25K
Publisher
Bureau of Safety and Environmental Enforcement
Type
Investigation Report
Date
Unknown
Topic
Functional Safety, Hydrocarbon Release, Pressure Systems
Equipment
Operator Displays and Control Interfaces, Process Pipework and Pipelines, Valve
Control
Alarm Management, Functional Testing, Operating and Work Procedures, Stop-Work Authority