Investigation Report

Arc Flash During Cleaning of Energised Motor Control Centre Busbars

BSEEBureau of Safety and Environmental Enforcement

02-07-2009 18:00 P00441 SM6374 1-LTA (1-3 days), 1 -LTA (>3 days) Required Evacuation

Read at BSEEOpens the document on bsee.gov

Summary

An accident investigation examines an arc flash during cleaning of energised motor control centre busbars with aerosol solvent and a steel-bristled brush. Findings identify missing work planning, permits and lockout procedures, alongside inadequate protective equipment. Recommendations address cabinet reinstatement planning, safe work permits and cleaning only with the centre de-energised.

Topics

About This Record
Original title
02-07-2009 18:00 P00441 SM6374 1-LTA (1-3 days), 1 -LTA (>3 days) Required Evacuation
Publisher
Bureau of Safety and Environmental Enforcement
Type
Investigation Report
Date
Unknown
Topic
Arc Flash, Electrical Safety
Activity
Electrical Work
Equipment
Hand Tools, Personal Protective Equipment, Switchgear
Control
Energy and Process Isolation, Job Safety Analysis, Lockout and Tagout, Permit to Work
Link
Checked , working
Record
bsee-8ba5015db5 · added 2 October 2026