Safety Alert
Safety Alert 1 - Flash Fire from Liquid Phase Heat Transfer Unit
Read at BSEEOpens the document on bsee.gov
Summary
A platform restart led to a flash fire after heat-transfer fluid overheated while circulating pumps were stopped and the burner valve remained operating. Pressure expansion ruptured the expansion tank. The alert recommends secondary relief with monthly and pre-start testing, burner–pump controls, pressure-rated expansion vessels and continuously operating heat sensors.