Investigation Report

Flash Fire After Line Heater Overflow onto Compressor Exhaust

BSEEBureau of Safety and Environmental Enforcement

02-02-2015 02:30 G01665 MP 288 A Fire

Read at BSEEOpens the document on bsee.gov

Summary

The investigation examines a flash fire at Main Pass 288-A after overheated glycol and antifreeze overflowed a line heater onto compressor exhaust. Findings address temperature-controller malfunction, failed protective shutdown and an obstructed burner viewing port. Recorded corrective actions include controller replacement, containment around the hatch and changes to level protection.