Safety Alert

Safety Alert 168 - Twisted Valve Stem and Ineffective Level Safety High Result in Oil Spill

BSEEBureau of Safety and Environmental EnforcementBSEE Safety Alert 168

Safety Alert 168 - Twisted Valve Stem and Ineffective Level Safety High Result in Oil Spill

Read at BSEEOpens the publisher’s page on bsee.gov

Summary

An oil spill followed separator cleaning when a twisted ball-valve stem left the drain partially open despite its handle position. Density differences prevented the sump tank’s level safety high from actuating. The alert recommends periodic valve holding checks where operationally feasible and reviewing atmospheric-tank level protection against this upset condition.

Topics

About This Record
Publisher
Bureau of Safety and Environmental Enforcement
Type
Safety Alert
Reference
BSEE Safety Alert 168
Date
19 August 1996
Topic
Barrier Management, Hydrocarbon Release, Mechanical Failure
Activity
Inspection and Maintenance
Equipment
Storage Tanks, Valve
Control
Functional Testing
Sector
Upstream Oil and Gas
Link
Checked , working
Record
bsee-safety-alert-168 · added 2 September 2026