Safety Alert

Safety Alert 256 - Carbon Monoxide Poisoning

BSEEBureau of Safety and Environmental EnforcementBSEE Safety Alert 256

Safety Alert 256 - Carbon Monoxide Poisoning

Read at BSEEOpens the publisher’s page on bsee.gov

Summary

Offshore platform personnel suffered carbon monoxide poisoning after natural gas engine fumes entered temporary accommodation through ventilation openings, principally the air conditioning fresh air inlet. The alert recommends reviewing accommodation placement relative to engine exhausts, installing carbon monoxide detectors, inspecting potential exhaust entry points and checking exhaust vent wind flaps.

Topics

About This Record
Publisher
Bureau of Safety and Environmental Enforcement
Type
Safety Alert
Reference
BSEE Safety Alert 256
Date
2 January 2008
Topic
Hazardous Substances, Respiratory Hazards
Activity
Inspection and Maintenance
Equipment
Gas Detector
Control
Functional Testing, Ventilation
Sector
Upstream Oil and Gas
Setting
Offshore Installation
Link
Checked , working
Record
bsee-safety-alert-256 · added 2 September 2026