Safety Alert
Improper Installation of Safety Device
Read at BSEEOpens the publisher’s page on bsee.gov
Summary
A heater treater incident involved readings above 1,000°F and a red-glowing stack before manual shutdown. The alert examines short thermowells and temperature indicators, Teflon tape impairing heat dissipation, and partially plugged arrestors. It recommends considering installation checks, scheduled maintenance and periodic inspection or replacement of safety devices.