Safety Alert
GEC Type VMX High Voltage Switchgear (including GEC Alsthom, Alstom or Areva T&D)
Read at HSEOpens the publisher’s page on hse.gov.uk
Summary
HSE safety notice addresses partial discharge and vacuum interrupter integrity in legacy GEC VMX high-voltage switchgear. Following a disruptive circuit-breaker failure involving arcing and fire, it recommends checking applicable design modifications, maintenance records and substation environmental conditions, alongside discharge surveys, integrity testing and revised access risk assessments.