Safety Alert

GEC Type VMX High Voltage Switchgear (including GEC Alsthom, Alstom or Areva T&D)

HSEUK Health and Safety ExecutiveCEMHD01-2026

GEC Type VMX High Voltage Switchgear (including GEC Alsthom, Alstom or Areva T&D)

Read at HSEOpens the publisher’s page on hse.gov.uk

Summary

HSE safety notice addresses partial discharge and vacuum interrupter integrity in legacy GEC VMX high-voltage switchgear. Following a disruptive circuit-breaker failure involving arcing and fire, it recommends checking applicable design modifications, maintenance records and substation environmental conditions, alongside discharge surveys, integrity testing and revised access risk assessments.

Topics

About This Record
Publisher
UK Health and Safety Executive
Type
Safety Alert
Reference
CEMHD01-2026
Date
May 2026
Topic
Ageing, Life Extension and Obsolescence, Electrical Safety, Regulation and Legislation
Activity
Electrical Work, Inspection and Maintenance
Equipment
Switchgear
Control
Functional Testing, Non-Destructive Testing, Preventive Maintenance, Risk Assessment
Link
Checked , working
Record
hse-cemhd01-2026 · added 2 September 2026