Safety Alert

Failure to detect dangerous gas/vapour due to incorrect specification of sample tube

HSEUK Health and Safety ExecutiveCEMHD1-2020

Failure to detect dangerous gas/vapour due to incorrect specification of sample tube

Read at HSEOpens the publisher’s page on hse.gov.uk

Summary

This safety alert examines misleading readings from pumped gas detectors caused by vapour adsorption inside unsuitable sampling tubes. A fatal explosion followed hot work based on a false reading. It recommends checking detector–tube combinations with the substance of interest where practicable and assessing sampling-system response times.

Topics

About This Record
Publisher
UK Health and Safety Executive
Type
Safety Alert
Reference
CEMHD1-2020
Date
10 September 2020 (added from another catalogue record)
Topic
Explosion, Hazardous Substances
Activity
Hot Work
Equipment
Gas Detector
Control
Functional Testing, Atmospheric Gas Testing
Sector
Downstream and Process Industries
Link
Checked , working
Record
hse-cemhd1-2020 · added 2 September 2026

Report a problem with this record