Summary
A crew member received an electrical shock while stripping insulation during replacement motor work. The isolation omitted a space-heater supply in the test position, and a generic motor drawing had been used. The flash stresses equipment-specific drawings in permit-to-work and lockout/tagout procedures when determining isolation.
Classifications: Electric shock; electrocution.
Classifications: Electrical safety; electrical hazards.
Classifications: Electrical isolation; electrical lockout.
Classifications: Electrical work; electrical maintenance.
Classifications: Energy and process isolation; isolation; energy isolation.
Classifications: Lockout and tagout; LOTO; lockout/tagout.
Classifications: Permit to work; PTW; work permit.
Summary
A worker received an electrical shock after an active heater supply was missed during equipment isolation.