Fire extinguisher fails during pressure testing
Fire extinguisher fails during pressure testing
- IMCA
- Safety Flash
- IMCA SF 25/23
- Hot Work and FireInspection and MaintenancePressure Systems
- Ageing, life extension and obsolescenceMechanical failurePressure systems
- Inspection and maintenancePressure testing
- Pressure vessel
- Competence and trainingPreventive maintenance
Summary
A 13-year-old, 5 kg CO2 fire extinguisher rated to 200 bar failed at 196 bar during a scheduled hydrostatic test intended to reach 300 bar. Nobody was harmed. The flash discusses ageing and integrity, alongside actions concerning maintenance reviews, age-sensitive testing plans, inspection records and personnel training.