Investigation Report

Heater Backfire During Platform Restart After Emergency Shutdown Testing

BSEEBureau of Safety and Environmental Enforcement
Read at BSEEOpens the document on bsee.gov

Summary

This investigation examines an Ambitrol heater backfire during platform restart following emergency shutdown testing. Inadequate purging, unreliable air/fuel ratio valve operation and excess fuel admitted by the programmable logic controller allowed an explosive mixture to accumulate. The heater cover was dislodged; no personnel injury, environmental incident or fire resulted.

Topics

About This Record
Original title
03-16-2015 16:30 G02719 HI A 582 Explosion / Structural Damage / Equipment Failure
Publisher
Bureau of Safety and Environmental Enforcement
Type
Investigation Report
Date
Unknown
Topic
Explosion, Functional Safety, Mechanical Failure
Activity
Inspection and Maintenance
Equipment
Valve
Control
Functional Testing, Stop-Work Authority
Sector
Upstream Oil and Gas
Setting
Offshore Installation
Link
Checked , working
Record
bsee-8b7a647513 · added 2 October 2026