Investigation Report

Heat-Tracing Fire on Offshore Platform

BSEEBureau of Safety and Environmental Enforcement

03-12-2008 07:50 G05889 GC/65 Fire - Required Muster

Read at BSEEOpens the document on bsee.gov

Summary

An investigation records a heat-tracing fire at the Bullwinkle platform. Damage or wear to the element was identified as the probable cause. A high-impedance arcing fault did not trip the breaker, and flames repeatedly returned after extinguishing. Electrical isolation stopped reignition; all personnel were accounted for during muster.

Topics

About This Record
Original title
03-12-2008 07:50 G05889 GC/65 Fire - Required Muster
Publisher
Bureau of Safety and Environmental Enforcement
Type
Investigation Report
Date
Unknown
Topic
Electrical Safety, Fire
Activity
Electrical Isolation
Control
Emergency Response, Fire Protection, Energy and Process Isolation