Safety Alert

Safety Alert 101 - Explosion

BSEEBureau of Safety and Environmental EnforcementBSEE Safety Alert 101

Safety Alert 101 - Explosion

Read at BSEEOpens the publisher’s page on bsee.gov

Summary

An alert describes a Gulf of Mexico platform explosion after a malfunctioning automatic control system was bypassed and a heater’s fuel shutdown valve removed from service. An employee attempted manual ignition without purging the firebox, suffering serious injury; the heater was destroyed. The operator subsequently instructed employees against bypassing burner controls.

Topics

About This Record
Publisher
Bureau of Safety and Environmental Enforcement
Type
Safety Alert
Reference
BSEE Safety Alert 101
Date
8 June 1981 (added from another catalogue record)
Topic
Explosion, Functional Safety
Equipment
Valve
Control
Ignition Source Control
Setting
Offshore Installation
Link
Checked , working
Record
bsee-safety-alert-101 · added 2 September 2026