Safety Alert

Safety Alert 132 - Supply Gas Fire

BSEEBureau of Safety and Environmental EnforcementBSEE Safety Alert 132

Safety Alert 132 - Supply Gas Fire

Read at BSEEOpens the publisher’s page on bsee.gov

Summary

An offshore platform flash fire occurred when cutting slag ignited supply gas leaking from a surface safety valve actuator O-ring during workover preparations. No injury or damage resulted. The alert records the operator’s planned closer leak checks, actuator depressurisation and firewater deluge activation to intercept sparks before the well bay.

Topics

About This Record
Publisher
Bureau of Safety and Environmental Enforcement
Type
Safety Alert
Reference
BSEE Safety Alert 132
Date
13 February 1985 (added from another catalogue record)
Topic
Fire, Hydrocarbon Release
Activity
Hot Work, Inspection and Maintenance, Well Intervention
Equipment
Valve
Control
Fire Protection, Energy and Process Isolation
Sector
Upstream Oil and Gas
Setting
Offshore Installation
Link
Checked , working
Record
bsee-safety-alert-132 · added 2 September 2026