Safety Alert

Safety Alert 176 - Mud Logging Unit Explosion and Fire

BSEEBureau of Safety and Environmental EnforcementBSEE Safety Alert 176

Safety Alert 176 - Mud Logging Unit Explosion and Fire

Read at BSEEOpens the publisher’s page on bsee.gov

Summary

An explosion and fire during mud logging unit setup involved hydrogen-fed analytical instruments. Connections had not been pressure-tested or checked for leaks, and damaged polyurethane hose allowed continued hydrogen flow. The alert recommends considering automatic shutdown, gas detection and positive purge arrangements, alongside piping material review and post-installation leak checks.

Topics

About This Record
Publisher
Bureau of Safety and Environmental Enforcement
Type
Safety Alert
Reference
BSEE Safety Alert 176
Date
22 July 1998 (added from another catalogue record)
Topic
Explosion, Fire, Hydrogen Safety
Equipment
Gas Cylinder, Gas Detector, Hose, Process Pipework and Pipelines
Control
Energy and Process Isolation, Pre-Use Checks
Sector
Upstream Oil and Gas
Link
Checked , working
Record
bsee-safety-alert-176 · added 2 September 2026