Safety Alert

Fire Tube Hazards Increase Risk of Flame Migration

BSEEBureau of Safety and Environmental EnforcementBSEE Safety Alert 397

Fire Tube Hazards Increase Risk of Flame Migration

Read at BSEEOpens the publisher’s page on bsee.gov

Summary

BSEE inspectors found warped flame-arrestor flanges and gaps after heater-treater and glycol-reboiler fire tubes were reinstalled using incompatible non-OEM fasteners. These defects created potential paths for flame migration. The alert recommends considering pre-startup reviews, OEM-recommended parts, more frequent visual inspections and checks of connections disturbed during maintenance.

Topics

About This Record
Publisher
Bureau of Safety and Environmental Enforcement
Type
Safety Alert
Reference
BSEE Safety Alert 397
Date
2 October 2020
Topic
Fire, Mechanical Failure
Activity
Inspection and Maintenance
Control
Ignition Source Control
Sector
Upstream Oil and Gas
Link
Checked , working
Record
bsee-safety-alert-397 · added 2 September 2026