Safety Alert 148 - Pipe Nipple Fatigue and Inadequate Insulation Cause Compressor Fire

BSEEBureau of Safety and Environmental EnforcementBSEE Safety Alert 148

Safety Alert 148 - Pipe Nipple Fatigue and Inadequate Insulation Cause Compressor Fire

Read at BSEEOpens the publisher’s page on bsee.gov

Summary

A failed all-thread nipple released gas that ignited at a compressor turbocharger. Stored filters and belts intensified the fire, while inadequate battery voltage prevented the fire-water pump engine from starting. The alert records firefighting arrangements and operator measures covering weekly battery checks, removal of stored items and insulation of hot components.

Topics

About This Record
Publisher
Bureau of Safety and Environmental Enforcement
Type
Safety Alert
Reference
BSEE Safety Alert 148
Date
27 March 1986 (added from another catalogue record)
Topic
Fire, Loss of Containment, Material Fatigue, Mechanical Failure
Activity
Inspection and Maintenance
Equipment
Process Pipework and Pipelines, Pumps
Control
Fire Protection, Functional Testing, Ignition Source Control, Preventive Maintenance