Safety Alert

Failure of pipeline emergency shut-down valve

HSEUK Health and Safety ExecutiveHID3-2010

Failure of pipeline emergency shut-down valve

Read at HSEOpens the publisher’s page on hse.gov.uk

Summary

HSE alerts operators to a spring-return pipeline emergency shutdown valve that failed open, disabling platform isolation. Initial indications linked retaining-rod failure to corrosion; released springs and an end plate presented stored-energy hazards. It calls for prompt inspection, conditional temporary restraints, actuator performance testing, coating and seal maintenance, and review of corrosion-resistant designs.

Topics

About This Record
Publisher
UK Health and Safety Executive
Type
Safety Alert
Reference
HID3-2010
Date
6 April 2010 (added from another catalogue record)
Topic
Barrier Management, Corrosion, Line of Fire, Mechanical Failure
Activity
Inspection and Maintenance
Equipment
Valve
Control
Functional Testing, Energy and Process Isolation, Preventive Maintenance
Sector
Upstream Oil and Gas
Setting
Offshore Installation
Link
Checked , working
Record
hse-hid3-2010 · added 2 September 2026