Summary
Testing of a vessel’s helideck foam sample revealed excessive water content, traced to a leaking non-return valve. The diluted concentrate could not have produced the required foam blanket during a helicopter fire. Company actions included leakage testing where possible, frequent planned inspection when convenient, and scheduling an isolation valve.
Classifications: Fire; fire safety.
Classifications: Mechanical failure; equipment failure.
Classifications: Inspection and maintenance; asset inspection; equipment maintenance.
Classifications: Storage tanks; atmospheric tanks.
Classifications: Valve; valves.
Classifications: Fire protection; fire suppression; fire detection.
Classifications: Functional testing; function test.
Classifications: Energy and process isolation; isolation; energy isolation.
Classifications: Preventive maintenance; preventative maintenance; planned maintenance.
Classifications: Marine industry; shipping industry; maritime sector.
Classifications: Helideck; helicopter landing deck.
Classifications: Vessel; aboard ship; onboard vessel.
Summary
Further to information provided in information note Firefighting foam on helidecks, we have been provided with the following information arising from a foam sample test onboard a vessel with a helideck.
IMCA SF 01/05. Themes: emergency response, helicopter and aviation, hot work and fire, inspection and maintenance.