Helideck foam sample

IMCAInternational Marine Contractors AssociationIMCA SF 01/05

Helideck foam sample

Read at IMCAOpens the publisher’s page on imca-int.com

Summary

Testing of a vessel’s helideck foam sample revealed excessive water content, traced to a leaking non-return valve. The diluted concentrate could not have produced the required foam blanket during a helicopter fire. Company actions included leakage testing where possible, frequent planned inspection when convenient, and scheduling an isolation valve.

Topics

About This Record
Publisher
International Marine Contractors Association
Type
Safety Flash
Reference
IMCA SF 01/05
Date
3 January 2005
Topic
Fire, Mechanical Failure
Activity
Inspection and Maintenance
Equipment
Storage Tanks, Valve
Control
Fire Protection, Functional Testing, Energy and Process Isolation, Preventive Maintenance
Sector
Marine Industry
Setting
Helideck, Vessel