Leak in hot water system for saturation divers

IMCAInternational Marine Contractors AssociationIMCA SF 01/24

Leak in hot water system for saturation divers

Read at IMCAOpens the publisher’s page on imca-int.com

Summary

A saturation-diving hot-water unit leaked through locally corroded pipework inaccessible for visual inspection. Diving was suspended because the remaining unit lacked backup. Repairs involved welding a sleeve over the leak and inspecting the other unit. The flash suggests considering wall-thickness measurements of old pipes.

Topics

About This Record
Publisher
International Marine Contractors Association
Type
Safety Flash
Reference
IMCA SF 01/24
Date
9 January 2024
Topic
Corrosion, Loss of Containment
Activity
Inspection and Maintenance, Saturation Diving
Equipment
Process Pipework and Pipelines
Control
Non-Destructive Testing, Stop-Work Authority