Failure of fire extinguishers owing to corrosion

IMCAInternational Marine Contractors AssociationIMCA SF 12/16

Failure of fire extinguishers owing to corrosion

Read at IMCAOpens the publisher’s page on imca-int.com

Summary

A safety flash describes a near miss found during mobilisation inspections of a relatively new fire extinguisher. Corrosion at the brass fitting and aluminium stem connection caused the stem to fall apart when touched. The cylinder showed no corrosion. The notice highlights dissimilar-metal corrosion in pressure vessels.

Topics

About This Record
Publisher
International Marine Contractors Association
Type
Safety Flash
Reference
IMCA SF 12/16
Date
6 May 2016
Topic
Corrosion, Mechanical Failure, Pressure Systems
Activity
Inspection and Maintenance
Equipment
Pressure Vessel