Safety Flash

Electrocution incident – make sure electrical equipment is safe!

IMCAInternational Marine Contractors AssociationIMCA SF 19/23

Electrocution incident – make sure electrical equipment is safe!

Read at IMCAOpens the publisher’s page on imca-int.com

Summary

A vessel cook suffered a mains electric shock while touching a bain-marie and messroom service window simultaneously. A detached earthing wire caused an earth fault in the heater element. The flash describes gaps in galley testing and maintenance, followed by fleetwide electrical testing, planned maintenance additions and revised risk assessment.

Topics

About This Record
Publisher
International Marine Contractors Association
Type
Safety Flash
Reference
IMCA SF 19/23
Date
3 August 2023
Topic
Electric Shock, Electrical Safety
Activity
Inspection and Maintenance
Control
Preventive Maintenance, Risk Assessment
Sector
Marine Industry
Setting
Vessel
Link
Checked , working
Record
imca-sf-19-23-electrocution-incident-make-sure-electrical-equipment-is-safe · added 1 September 2026