Safety Flash

Fatality: Overpressure of an explosion-proof enclosure

IMCAInternational Marine Contractors AssociationIMCA SF 24/17

Fatality: Overpressure of an explosion-proof enclosure

Read at IMCAOpens the publisher’s page on imca-int.com

Summary

An engineer suffered fatal head injuries when trapped pressure propelled an explosion-proof enclosure cover during removal. Leaking sample gas or instrument air components had pressurised the enclosure, which lacked pressure indication and relief. Lessons address identifying susceptible enclosures and developing mitigation with manufacturers while preserving electrical certification.

Topics

About This Record
Publisher
International Marine Contractors Association
Type
Safety Flash
Reference
IMCA SF 24/17
Date
5 October 2017
Topic
Electrical Safety, Line of Fire, Pressure Systems
Control
Pressure Relief
Link
Checked , working
Record
imca-sf-24-17-fatality-overpressure-of-an-explosion-proof-enclosure · added 1 September 2026