Safety Flash

Electrician suffered flash burn to hand

IMCAInternational Marine Contractors AssociationIMCA SF 26/21

Electrician suffered flash burn to hand

Read at IMCAOpens the publisher’s page on imca-int.com

Summary

An electrician suffered a hand flash burn while checking insulation on a 690-volt bus bar aboard a vessel in dry dock. The switchboard became live after an unguarded status switch changed and the power management system closed a breaker. Lessons address isolation, shipyard work permits, supervision and communication.

Topics

About This Record
Publisher
International Marine Contractors Association
Type
Safety Flash
Reference
IMCA SF 26/21
Date
22 September 2021
Topic
Arc Flash, Electrical Safety, Hand and Finger Injuries
Activity
Electrical Isolation, Electrical Work
Equipment
Switchgear
Control
Lockout and Tagout, Operational Supervision, Permit to Work, Risk Assessment
Sector
Marine Industry
Setting
Vessel
Link
Checked , working
Record
imca-sf-26-21-electrician-suffered-flash-burn-to-hand · added 1 September 2026