Investigation Report

Electrical Arcing and Fire in Jack-Up Rig SCR Room

BSEEBureau of Safety and Environmental Enforcement

06-24-2008 08:00 G24718 WC/202 Fire

Read at BSEEOpens the document on bsee.gov

Summary

An investigation describes electrical arcing and fire in the Hercules 253 jack-up rig’s SCR room. Accumulated soot and contaminants provided a conductive path between generator busbars and ground. The report identifies inadequate inspection and maintenance as contributing factors and recommends regular SCR panel inspections with maintenance programmes based on their findings.

Topics

About This Record
Original title
06-24-2008 08:00 G24718 WC/202 Fire
Publisher
Bureau of Safety and Environmental Enforcement
Type
Investigation Report
Date
Unknown
Topic
Arc Flash, Electrical Safety, Fire
Activity
Inspection and Maintenance
Equipment
Switchgear
Control
Preventive Maintenance
Sector
Upstream Oil and Gas
Setting
Offshore Installation
Link
Checked , working
Record
bsee-07c314915d · added 2 October 2026