Safety Alert
Electrical Fire Damages Equipment in Motor Control Center
Read at BSEEOpens the publisher’s page on bsee.gov
Summary
An offshore platform motor control centre fire followed circuit-breaker engagement. Analysis identified loose or damaged bus-bar fasteners, damaged insulation and dust that likely caused an arc. BSEE recommends considering inspection and maintenance procedures, thermography, insulation-resistance and polarisation-index testing, torque checks and component replacement schedules.