Investigation Report
Partial Power Loss Disables Safety Systems During Generator Fuel Switching
05-06-2019 07:48 G33733 MC 437 Damaged/Disabled Safety Sys.
- BSEE
- Investigation Report
- Unknown
- Functional safety
- Inspection and maintenance
- Safety communication
- Upstream oil and gas
- Offshore installation
Summary
BSEE investigates partial power loss at the Appomattox platform during generator fuel switching. Failed UPS capacitors and undersized fuses disabled the fire and gas processor, preventing emergency generator starting. Bypassing the UPS restored this capability. No injuries or pollution were reported; the facility had not begun oil production.
Classifications: Functional safety; safety instrumented systems; SIS.
Classifications: Inspection and maintenance; asset inspection; equipment maintenance.
Classifications: Safety communication; toolbox talk; toolbox talks.
Classifications: Upstream oil and gas; oil and gas extraction; upstream petroleum.
Classifications: Offshore installation; offshore platform; offshore rig.