Investigation Report

Platform Fire Involving Fuel-Gas Piping and Heat-Trace Junction Box

BSEEBureau of Safety and Environmental Enforcement

04-27-2006 05:30 G02323 EI/360 Fire

Read at BSEEOpens the document on bsee.gov

Summary

This investigation examines a platform fire involving corroded, insulated fuel-gas piping and an apparently faulty heat-trace junction box. Emergency shutdown removed power from a temporary firewater pump that lacked an emergency-bus connection. The report documents firefighting and mustering, and recommends piping inspections, suitable circuit protection and standardised temporary-generator arrangements.

Topics

About This Record
Original title
04-27-2006 05:30 G02323 EI/360 Fire
Publisher
Bureau of Safety and Environmental Enforcement
Type
Investigation Report
Date
Unknown
Topic
Corrosion, Electrical Safety, Fire, Hydrocarbon Release
Activity
Inspection and Maintenance
Equipment
Process Pipework and Pipelines, Pumps
Control
Competence and Training, Evacuation, Escape and Rescue, Fire Protection, Ignition Source Control
Sector
Upstream Oil and Gas
Setting
Offshore Installation
Link
Checked , working
Record
bsee-d37606576e · added 2 October 2026

Report a problem with this record