Safety Alert

Safety Alert 17 - Electrical Wiring Inspection And Maintenance

BSEEBureau of Safety and Environmental EnforcementBSEE Safety Alert 17

Safety Alert 17 - Electrical Wiring Inspection And Maintenance

Read at BSEEOpens the publisher’s page on bsee.gov

Summary

Two electrical fires on Pacific OCS platforms involved cracked control-panel wiring insulation and a failed generator rotor winding. Neither caused injuries. Against a background of ageing equipment, the alert recommends that operators consider periodic visual inspection, insulation-resistance testing and thermal imaging, with maintenance where problems are detected.

Topics

About This Record
Publisher
Bureau of Safety and Environmental Enforcement
Type
Safety Alert
Reference
BSEE Safety Alert 17
Date
23 July 2003 (added from another catalogue record)
Topic
Ageing, Life Extension and Obsolescence, Electrical Safety, Fire
Activity
Electrical Work, Inspection and Maintenance
Equipment
Rotating Machinery
Control
Thermography
Sector
Upstream Oil and Gas
Setting
Offshore Installation