Safety Alert

Safety Alert 228 - Vent Gas Migrates Through Cable Entrance Hole, Motor Control Center Explodes

BSEEBureau of Safety and Environmental EnforcementBSEE Safety Alert 228

Safety Alert 228 - Vent Gas Migrates Through Cable Entrance Hole, Motor Control Center Explodes

Read at BSEEOpens the publisher’s page on bsee.gov

Summary

An offshore platform explosion followed compressor start failure and gas migration from skimmer tank vents into a motor control centre. Opening the door created a chimney effect; a pump relay ignited gas trapped in electrical panels. MMS recommends sealing openings, periodic inspections and measures preventing discharge through skimmer vents.

Topics

About This Record
Publisher
Bureau of Safety and Environmental Enforcement
Type
Safety Alert
Reference
BSEE Safety Alert 228
Date
24 March 2005 (added from another catalogue record)
Topic
Electrical Safety, Explosion, Hydrocarbon Release
Activity
Inspection and Maintenance
Equipment
Process Pipework and Pipelines, Storage Tanks, Switchgear, Valve
Sector
Upstream Oil and Gas
Setting
Offshore Installation
Link
Checked , working
Record
bsee-safety-alert-228 · added 2 September 2026