Summary

This alert addresses two industrial UPS fires involving overheating ICAR self-healing polypropylene capacitors in 2011 and 2018. It advises dutyholders to consider prompt replacement of affected models and review cooling requirements. Capacitance testing and visible bulging or discolouration may not reliably indicate these capacitors’ remaining service life.