BSEE Safety Alert 514 - Verify Megger Testing and Termination Prep to Prevent Seawater Pump Motor Fires

Read at BSEEOpens the document on bsee.gov

Summary

A seawater pump motor fire followed termination repairs. Findings identified insulation testing at a lower voltage than required, resistance below the work-pack threshold and inadequate semiconductor-layer preparation. BSEE recommends considering adherence to repair instructions, verification of test arrangements and results, correctly rated testers and worker understanding of resistance units.