Safety Flash

Near-miss: Failure to reconnect fire suppression systems

IMCAInternational Marine Contractors AssociationIMCA SF 04/14

Near-miss: Failure to reconnect fire suppression systems

Read at IMCAOpens the publisher’s page on imca-int.com

Summary

A vessel inspection revealed that six of ten FM200 fire-suppression cylinders remained disconnected following dry docking. The isolation certificate was missing despite a register entry recording reinstatement. All cylinders were restored, and the member introduced a return-to-service procedure, reviewed maintenance routines and developed a safety inspection checklist.

Topics

About This Record
Publisher
International Marine Contractors Association
Type
Safety Flash
Reference
IMCA SF 04/14
Date
4 April 2014
Topic
Fire
Activity
Inspection and Maintenance
Equipment
Gas Cylinder
Control
Fire Protection, Energy and Process Isolation, Operating and Work Procedures, Preventive Maintenance
Sector
Marine Industry
Setting
Vessel
Link
Checked , working
Record
imca-sf-04-14-near-miss-failure-to-reconnect-fire-suppression-systems · added 1 September 2026