Summary

A worker died from flying debris when a fire extinguisher exploded while tackling a small fire. The report attributes the incident to cylinder corrosion beneath a rubber protective foot following water ingress. A vendor warning states that annual inspection should include examining the cylinder bottom with the foot removed.