Safety Flash

Unexpected Release of Water During Annual Maintenance of CO2 Fixed Firefighting System

IMCAInternational Marine Contractors AssociationIMCA SF 06/18

Unexpected Release of Water During Annual Maintenance of CO2 Fixed Firefighting System

Read at IMCAOpens the publisher’s page on imca-int.com

Summary

During annual maintenance of a vessel’s fixed CO2 firefighting system, air blown through lines at 7 bar unexpectedly discharged water onto electrical switchboards and transformers. The water source remained unidentified, with condensation suspected. Work stopped, nozzle covers were introduced and maintenance instructions revised; compressed-air systems should be blown through before connection.

Topics

About This Record
Publisher
International Marine Contractors Association
Type
Safety Flash
Reference
IMCA SF 06/18
Date
19 March 2018
Topic
Electrical Safety
Activity
Inspection and Maintenance
Equipment
Switchgear
Control
Operating and Work Procedures, Preventive Maintenance, Stop-Work Authority
Sector
Marine Industry
Setting
Vessel
Link
Checked , working
Record
imca-sf-06-18-unexpected-release-of-water-during-annual-maintenance-of-co2-fixed-firefighting-system · added 1 September 2026

Report a problem with this record