Safety Flash

MAIB: Blockage of fixed CO2 fire extinguishing system pilot hoses

IMCAInternational Marine Contractors AssociationIMCA SF 10/22

MAIB: Blockage of fixed CO2 fire extinguishing system pilot hoses

Read at IMCAOpens the publisher’s page on imca-int.com

Summary

Following a cargo ship engine-room fire, blocked pilot hoses were found to have impaired CO2 suppression. Couplings had not been fully bored through, and servicing tests had missed blockages and leaks. The flash highlights manual activation procedures and pneumatic flow testing of complete hose assemblies.

Topics

About This Record
Publisher
International Marine Contractors Association
Type
Safety Flash
Reference
IMCA SF 10/22
Date
21 April 2022
Topic
Fire, Mechanical Failure
Activity
Inspection and Maintenance
Equipment
Hose
Control
Fire Protection, Functional Testing, Operating and Work Procedures