Investigation Report

Safety warning issued after discovery of blocked fixed CO2 fire extinguishing system pilot hoses

MAIBMarine Accident Investigation Branch

Safety warning issued after discovery of blocked fixed CO2 fire extinguishing system pilot hoses

Read at MAIBOpens the publisher’s page on gov.uk

Summary

This bulletin examines blocked pilot hoses discovered after Finnmaster’s engine-room fire in Hull. Incompletely bored couplings prevented gas passage, while servicing tests missed blockages and leaks. It describes radiographic examination, revised pneumatic flow testing and recommendations to rectify affected assemblies and improve purchasing and quality control.

Topics

About This Record
Publisher
Marine Accident Investigation Branch
Type
Investigation Report
Date
10 March 2022
Topic
Fire, Mechanical Failure
Activity
Inspection and Maintenance
Equipment
Gas Cylinder, Hose
Control
Fire Protection, Functional Testing, Non-Destructive Testing
Sector
Marine Industry
Setting
Vessel
Link
Checked , working
Record
maib-safety-warning-issued-after-discovery-of-blocked-fixed-co2-fire-extinquishing-system · added 2 September 2026