Safety Alert

Safety Alert 143 - Compressor Fire During Maintenance Operation

BSEEBureau of Safety and Environmental EnforcementBSEE Safety Alert 143

Safety Alert 143 - Compressor Fire During Maintenance Operation

Read at BSEEOpens the publisher’s page on bsee.gov

Summary

A compressor engine inspection led to a fire when an arc from a disconnected spark plug wire ignited leaking starter gas. A loose pipe union and worn starter valve were identified. The operator planned revised exhaust piping, valve component replacement and spark-free ignition checks. No personnel were injured.

Topics

About This Record
Publisher
Bureau of Safety and Environmental Enforcement
Type
Safety Alert
Reference
BSEE Safety Alert 143
Date
15 August 1985 (added from another catalogue record)
Topic
Fire, Loss of Containment, Mechanical Failure
Activity
Inspection and Maintenance
Equipment
Hose, Process Pipework and Pipelines, Valve
Control
Ignition Source Control
Link
Checked , working
Record
bsee-safety-alert-143 · added 2 September 2026

Report a problem with this record