Safety Alert

Mechanical Failure of LACT Pump Caused Fire

BSEEBureau of Safety and Environmental EnforcementBSEE Safety Alert 518

Mechanical Failure of LACT Pump Caused Fire

Read at BSEEOpens the publisher’s page on bsee.gov

Summary

An offshore production facility fire followed LACT charge-pump misalignment after motor replacement. Excessive vibration loosened casing fasteners, allowing oil leakage; coupling failure caused further damage. The alert identifies omitted angular alignment and incorrect bolt torques, and recommends manufacturer-compliant installation, personnel training, review of post-installation surveillance and investigation of abnormal operation.

Topics

About This Record
Publisher
Bureau of Safety and Environmental Enforcement
Type
Safety Alert
Reference
BSEE Safety Alert 518
Date
1 July 2026
Topic
Fire, Hydrocarbon Release, Mechanical Failure
Activity
Inspection and Maintenance
Equipment
Pumps, Rotating Machinery
Control
Alarm Management, Competence and Training, Operating and Work Procedures
Sector
Upstream Oil and Gas
Setting
Offshore Installation