Safety Flash

Corrosion damage: Failed fire hydrant

IMCAInternational Marine Contractors AssociationIMCA SF 35/16

Corrosion damage: Failed fire hydrant

Read at IMCAOpens the publisher’s page on imca-int.com

Summary

A vessel’s hydrant valve assembly failed under pressure during helideck firefighting-system testing, struck the deck head and fell without injuring anyone. Analysis attributed stud failure to chloride-induced stress corrosion cracking and unsuitable material specification. Incorrect system operation contributed water hammer; actions included replacing affected studs and considering tropical-environment susceptibility.

Topics

About This Record
Publisher
International Marine Contractors Association
Type
Safety Flash
Reference
IMCA SF 35/16
Date
20 December 2016
Topic
Corrosion, Dropped Objects, Mechanical Failure, Pressure Systems, Structural and Asset Integrity
Activity
Inspection and Maintenance
Equipment
Valve
Control
Fire Protection
Sector
Marine Industry
Setting
Vessel
Link
Checked , working
Record
imca-sf-35-16-corrosion-damage-failed-fire-hydrant · added 1 September 2026

Report a problem with this record