Fire in incinerator exhaust gas manifold

IMCAInternational Marine Contractors AssociationIMCA SF 19/19

Fire in incinerator exhaust gas manifold

Read at IMCAOpens the publisher’s page on imca-int.com

Summary

A vessel incinerator fire followed undetected flame failure, continued sludge pumping and subsequent reignition by the automatic diesel burner. An incorrectly set control resistor and a tampered exhaust sensor were identified. The flash describes firefighting and shutdown effects, and recommends testing flame-failure devices through planned maintenance.

Topics

About This Record
Publisher
International Marine Contractors Association
Type
Safety Flash
Reference
IMCA SF 19/19
Date
12 August 2019
Topic
Fire, Functional Safety
Activity
Inspection and Maintenance
Control
Emergency Response, Fire Protection, Functional Testing, Preventive Maintenance