Summary
During monthly testing, a fire-fighting monitor’s water jet damaged a nearby MF/HF whip antenna. Investigation identified incorrect adjustment of the turning limit switch following contractor maintenance. The flash describes resetting the operating sector and recommends post-maintenance acceptance testing, verification of safety limits before tests and stopping unsafe work.